Central Power Research Institute, India
+91 80 22072207 +91 80 23601213 awasthi@cpri.in kamalasr@cpri.in ramdas@cpri.in Visit website
Prof.Sir.C.V.Raman Road, P.B.No: 8066, Sadashivanagar P.O
Bangalore, Karnataka, 560080
India
Overview
Key Contact Personnel:
V.S. Nandakumar, Director Generaldgcpri@cpri.in
R. A. Deshpande, Additional Director rad@cpri.in
Mehra.B.M, Additional Director mehra@cpri.in
wadhwani@cpri.in
Anupam Awasthi, Additional Director awasthi@cpri.in
Sudhakara Reddy.S, Additional Director ssreddy@cpri.in
Sheshagiri Rao.U.R, Additional Director urshesh@cpri.in
prabhakar@cpri.in
Dr. Pradeep M Nirgude, Additional Director pmnirgude@cpri.in
Meena.K.P, Joint Director meena@cpri.in
Year Founded:
HV Lab: 1970
UHVRL: 1993
HP Lab: 1990
STDS:1960
RTL Noida: 2009
Total Number of Employees: 481
Major Export Markets Served: Countries of Middle East / Far East / South East Asia, USA, Europe, Russia, Africa, SAARC.
Services
High Voltage Laboratory
Number of Employees:
• HV, Bangalore: 18
• UHV Research Laboratory, Hyderabad: 42
• STDS, Bhopal: 15
• RTL, Noida: 10
• CDD, Bangalore: 14
Dimensions of Main Test Halls:
• HV, Bangalore: 54 m length x 52 m width x 42 m height
• HV, Impulse Current Laboratory, Bangalore: 33 m length x 13 m width x 6 m height
• UHV Research laboratory, Hyderabad: Impulse Test Bay: 2080 sq. m
– Power Frequency Test Bay: 600 sq. m
– DC Test Bay: 1600 sq. m
– Indoor Shielded Laboratory: 50m length x 35m width x 35 m height
• STDS, Bhopal: 28m length x 24m width x 26m height
• RTL, Noida: 23m length x 15m width x 7.5m height
Dimensions of Secondary Test Halls:
• HV, Bangalore: Outdoor 55 m x 55 m
• UHV Research Laboratory, Hyderabad: Auxiliary Test Bay: 385 sq.m
• CDD, Bangalore: Indoor Lab 35m length x 25m breadth x 16m height
Outdoor test bay: 100m x 50m
Dielectric Testing Facilities:
Impulse Testing: | Max. Volt./Current | Standard |
Lightning Impulse | 3 MV, 150 kJ(HV, Bangalore) 2.4MV, 240kJ (STDS, Bhopal) 5 MV, 500 kJ (UHVRL, Hyderabad) 2.4MV, 240kJ (CDD, Bangalore) 1MV, 100kJ (RTL, Noida) |
IEC, ANSI, BS, IS |
Switching Impulse (Dry) | 1.6 MV (HV, Bangalore) 3.2 MV (UHVRL, Hyderabad) |
IEC, ANSI, BS, IS |
Switching Impulse (Wet) | 1.6 MV (HV, Bangalore) 3.2 MV (UHVRL, Hyderabad) |
IEC, ANSI, BS, IS |
Current Impulse | 100 kV, 300 kJ(HV, Bangalore) | IEC 60099-4 |
A.C. Testing: | ||
Dry & Wet | 1100 kV (HV, Bangalore) 1600 kV (rms)(UHVRL, Hyderabad) 350 kV (rms) (STDS, Bhopal) 250 kV (rms) (RTL, Noida) |
|
Wet | 1100 kV (rms) (HV, Bangalore) 1600 kV (rms) (UHVRL, Hyderabad) 350 kV (rms) (STDS, Bhopal) |
|
D.C. Testing: | ||
Dry | +/- 1200 kV / 200 mA(UHVRL, Hyderabad) +/- 320 kV / 15mA (HV, Bangalore) |
|
Wet | +/- 1200 kV / 200 mA(UHVRL, Hyderabad) | |
Partial Discharge & RIV Testing: | ||
1200 kV (AC), +/- 1200 kV (DC)(UHVRL, Hyderabad) 400 kV AC (HV, Bangalore) – RIV Test |
||
Capacitance & Tan ∂ Testing: | ||
1200 kV (AC) (UHVRL, Hyderabad) | ||
Corona | ||
±1200 kV (AC) (UHVRL, Hyderabad) ±1200 kV (DC) (UHVRL, Hyderabad) 400 kV (AC) (HV, Bangalore) |
Pollution Testing:
Dimension of Main Test Chambers:HV, Bangalore: 12m length x 12m width x 12m height
UHVRL, Hyderabad: 24 m (diameter) x 27 m (height) with 800 kV wall bushings
Standard | Max.A.C. Volt | Max.D.C. Volt | Temperature | |
Salt Fog | IEC 60507 | 800 kV AC System (UHVRL, Hyderabad) | — | — |
IEC 60507 | 400 kV AC System (HV, Bangalore) | — | — | |
Clean Fog | IEC 60507 | 132 kV System (HV, Bangalore) | — | Ambient |
IEC 60507, IEC TS 61245 | 765 kV System (UHVRL, Hyderabad) | 800 kV (UHVRL, Hyderabad) | — |
Ageing Tests: 1000 hrs Salt Fog Ageing Tests, Ageing Tests on Arrester Blocks
Other Testing Facilities
Max. Voltage | Max. Power | Frequency | Standard | |
Transformer Testing (HV, Bangalore) | ||||
Single Phase | 400 kV | 100 MVA | 50 Hz | IEC, BIS, ANSI |
Three Phase | 400 kV | 100 MVA | 50 Hz | IEC, BIS, ANSI |
Transformer Testing (UHVRL, Hyderabad) | ||||
Single Phase | 1200 kV | 500 MVA | 50 Hz | IEC, BIS, ANSI |
Three Phase | 1200 kV | 500 MVA | 50 Hz | IEC, BIS, ANSI |
Transformer Testing (RTL, Noida) | ||||
Single Phase | 132kV | 12 MVA | 50 Hz | IEC, BIS, ANSI |
Three Phase | 132kV | 12 MVA | 50 Hz | IEC, BIS, ANSI |
HV Cable Testing:
Max. Volt./Current | Standard/Remarks | |
Load Cycling | Up to 400 kV Cables | |
AC Voltage | 400 kV Class Cable (CDD, Bangalore)
33kV Class Cable (RTL, Noida) |
|
DC Voltage | 33kV Class Cable (CDD, Bangalore & RTL, Noida) | |
Lightning Impulse | Up to 400kV Class (CDD, Bangalore) | IEC, CENELEC, VDE, BIS |
33kV Class Cable (RTL, Noida) | IEC, CENELEC, VDE, BIS | |
Switching Impulse | 145 kV and 245 kV (HV, Bangalore) | IEC, CENELEC, VDE, BIS |
Test Loop Length: | 30m Type Test loop (CDD, Bangalore)
100 metres (Pre-qualification test) 15m Type Test (RTL, Noida) |
High Power Laboratory
Total Number of Employees:
• HPL, Bangalore: 30
• STDS, Bhopal: 41
HPL, Bangalore:
• Possible Power Frequency: 50/60 Hz
• Max. MVA: 2500, 14kV, 120 kA Short Circuit Generator
• Max. kV: 336 kV
Single Phase, 72.5 kV Three Phase
• Max. kA & Duration: 300 kArms STC for 1 sec.
• Max. kV: 400 kV DC Synthetic installation
• Synthetic Installation: 245kV Circuit Breaker, 63kA – Full Pole Testing, 400 kV Circuit Breaker – Unit Testing
STDS, Bhopal:
• Possible Power Frequency: 50Hz
• Max. MVA: Two Nos. of 1500 MVA Short Circuit Generators, 100 MVA Grid Sourced lab
• Max. kA & Duration: 200 kA STC for 1 sec.
Electrical Tests
• Medium Voltage Tests:Up to 36 kV Circuit Breakers-26.3 kA,
Power Transformers up to 250 MVA and voltage rating 220 kV class, up to 120 MVA and voltage rating 400 kV Class (HPL, Bangalore), Power Arc Test on insulator strings up to 40 kA for voltage class up to 400kV.
• Other Types of High Power Tests Offered: Short Time current Test on Reactors, Line Traps, Pressure Relief Tests on Lightning Arresters, Breaking Capacity Test on Fuses, Induced Current Switching Tests on High Voltage Earthing Switches. Internal Arc Tests on Panels, Internal Arc Tests on Instrument Transformers, Low Induction current switching Tests, Breaking Capacity Tests on OLTC, all tests on LV Switchgears as per IEC 61439-1 & 2. Mechanical Operation test on Circuit Breakers.
Other Test Capabilities
Testing of Transmission Line Towers; Overhead Conductors and Accessories; Seismic Qualification Tests; Testing of Power Capacitors, APFC Panels and Environmental Tests; Conformance Protocol Testing in accordance with IEC 61850, Testing Solar Products like Grid Tied Inverters, LED’s, Solar PV modules; Real Time Digital Simulator; Comprehensive test facilities for Energymeters, Transformer Oil.